Se rendre au contenu

Type 2 parafoudre Teco 1p+N 335V

https://crm.teconex.be/web/image/product.template/62098/image_1920?unique=68edac9
against overvoltages caused by indirect lightning strikes or transient overvoltages

1 varistor (L-N) + 1 spark gap (N-PE) (detachable)

visual indication to check varistor and spark gap status

35mm rail mounting (EN60715)

SPD type T2 to EN 61 643-11
class II testing to IEC 64643-1-A1

for single-phase TN-S or TT networks

permissible temperature range: -40°C to +70°C

terminal tightening torque: 2.4 - 3Nm

terminal capacitance: 4 - 25mm² max.

max. upstream fuse: 125A gLn I(cu) = 50kA
max. upstream circuit breaker: 100A, curve C, I(cu) = 20kA

load time (voltage rise 5kV/µs):
L-N: < 25ns
N-PE: < 100ns
L-PE: < 100ns

142,79 € 142.79 EUR 142,79 € Hors taxes

Pas disponible à la vente

  • U(p) à I(n)
  • frequenceMax
  • frequenceMin
  • Code
  • No. of modules
  • 820
  • U(n) L-N (5s)
  • U(n) N-PE (200ms)
  • I(n) 8/20 µs

Cette combinaison n'existe pas.

U(p) à I(n): < 1650 V V
frequenceMax: 60 Hz
frequenceMin: 50 Hz
Code: 173968
No. of modules: 2
820: 40 kA
U(n) L-N (5s): 335 Vac
U(n) N-PE (200ms): 280 Vac
I(n) 8/20 µs: 20 kA